Home»Products »Special AC Drive » ALPHA6600 Series AC Drive for Constant Pressure Water Supply System

ALPHA6600 Series AC Drive for Constant Pressure Water Supply System

ALPHA6600 series AC drive for constant pressure water supply system fully utilizes the hardware advantages of ALPHA6000. It has high performance andcan drive 4 sets motors (drive 2 motors in circular running) without watercontrol card/controller, which provides excellent drive and control solution inwater supply and HVAC industry.

Technical Characteristics

Voltage fluctuation range is ±20%.

Composed of the AC drive and the PID regulator.

Comprehensive watersupply solution; flexible configuration of general pump, fire pump, and pump with sleep mode; easy to realize automation of water supply pump system;circular pump mode: drive 2 motors; fixed pump mode: drive 4 motors

Keep constant pressure under any flow condition

Simple setup anddiagnosing on pumps

Make pumps runalternatively based on its working time to avoid the pump’s unbalanced wear

Turn on/off subsidiary pumps according to the technical specifications; control the variable pump to ensure continuous flow changing

When one single variable-speed pump fails to meet requirement of complete flow range, the system adopts one variable-speed pump and multiple fixed speed pumps (Max. 4units) with built-in PID regulating the pumps and pressure sensor giving feedback

Applications

The AC drive is ideal for use in the non-tower water feeder, non-negative pressure water supply system, the residential water supply system, as well as the urban central heating and water supply system.

Technical Specifications of ALPHA6600

Item Specification
Power Range 380V ±20% three phases: from 1.5 to 400kW
Rated Input Voltage and Frequency 380V three phases: 50/60Hz
Allowable Input Voltage Range 380V three phases: from 304 to 456V, Voltage unbalance rate of less than 3%, Frequency fluctuation of below ±5%
Rated Output Voltage From 0 to rated input voltage
Max. Overload Current P model: 120% for 3 seconds, 150% for one second
Control Method V/F control
Frequency Range From 0.00 to 650.00Hz (from 31R5PB to 35R5PB)
From 0.00 to 400.00Hz (from 37R5PB to 3400P)
Frequency Accuracy Digital command ± 0.01% (from -10℃ to +40℃)

Simulation command ± 0.01% (25℃ ± 10℃)
Preset Frequency Resolution Digital command 0.01Hz
Simulation command 1/1000 of the maximum frequency
Output Frequency Resolution 0.01Hz
Preset Frequency Signal From 0 to 10V, from 0 to 20mA
Torque Boost Automatic or manual operation (from 0.1 to 30.0%)
Acceleration-Deceleration Modes Straight line, or user-defined S curve
Acceleration-Deceleration Time From 0.1 to 3600 seconds (The acceleration and deceleration time are set individually.)
Braking Torque The additional braking resistance reaches up to 125%.
Voltage-Frequency Characteristics There are 4 fixed V/F characteristics for option, and any V/F characteristic can be preset. The V/F control with PG is provided.
Protective Functions Over-voltage, under-voltage, current limit, over-current, overload, electronic thermal relay, overheating, over-voltage stall, load short circuit, grounding, under-voltage protection, input phase loss, output phase loss, short circuit to ground, interphase short circuit, motor overload protection, etc
Ambient Temperature From -10℃ to +40℃
Humidity From 5 to 95% RH (No condensation)
Storage Temperature From -40℃ to +70℃
Service Place Indoor (without any corrosive gas)
Installation Site The altitude is at most 1,000m. There is not any dust, corrosive gas, or direct solar radiation.
Vibration Less than 5.9m/s2 (0.6g)
Protection Rating IP20
Cooling Method Forced air cooling
All our machines of below 22kW come with fans.

ALPHA6600 Selection Table

Voltage Classes Model Motor Power (kW) Rated Output Current (A)
380V Three Phases 6600-31R5PB 1.5 4
6600-32R2PB 2.2 6
6600-3004PB 3.7 9
6600-35R5PB 5.5 13
6600-37R5PB 7.5 17
6600-3011PB 11 25
6600-3015PB 15 32
6600-3018PB 18.5 37
6600-33022P 22 45
6600-3030P 30 60
6600-3037P 37 75
6600-3045P 45 90
6600-3055P 55 110
6600-3075P 75 150
6600-3093P 90 176
6600-3110P 110 210
6600-3132P 132 250
6600-3160P 160 300
6600-3185P 185 340
6600-3200P 200 380
6600-3220P 220 415
6600-3250P 250 470
6600-3280P 280 520
6600-3315P 315 600
6600-3355P 350 640
6600-3400P 400 750

Overall Dimension of ALPHA6600 Series AC Drive for Constant Pressure Water Supply System

Model H H1 W W1 D D1 D2 D3 d
6600-31R5PB 180 169 115 105 150 158 85 120 4.5
6600-32R2PB
6600-3004PB
6600-35R5PB 195 173 130 108 157 167 100 130 4.5

Model H H1 W W1 D D1 D2 d
6600-37R5PB 270 255 190 175 176 186 122 7
6600-3011PB

Model H H1 W W1 D D1 D2 d d 1
6600-3015PB 373 360 235 200 176 188 125 7 12
6600-3018PB
6600-33022P 420 405 270 200 218 230 175 7 14
6600-3030P
6600-3037P 503 488 311 200 230 242 180 7 14
6600-3045P
6600-3055P 590 570 351 200 254 266 192 10 20
6600-3075P
6600-3093P 698 672 400 280 260 272 186 12 22
6600-3110P
6600-3132P 850 823 505 420 280 292 212 12 22
6600-3160P

Installation Size of 380V 160-355kW Three-Phase Standard Model with Base

Model W1 W2 W3 H1 H2 D1 D2 D3 d 1 d 2
6600-3185P 600 200 530 1380 1360 400 280 60 3-φ 14 4-φ 14
6600-3200P
6600-3220P
6600-3250P
6600-3280P 800 300 730 1535 1515 410 288 60 3-φ 14 4-φ 14
6600-3315P
6600-3355P
6600-3400P

Installation Size of 380V 160~355kW Three-Phase Standard Model with Wall Mount

Model W1 W2 H1 H2 D1 D2 D3 d 1
6600-3185P 600 200 1026 1360 400 245 77 6-φ 14
6600-3200P
6600-3220P
6600-3250P
6600-3280P 800 300 1180 1515 410 250 88 6-φ 14
6600-3315P
6600-3355P
6600-3400P

Installation Size of 380V 160-500kW Three-Phase Narrow-Body Model

Model W W1 D H a b c d
6600-3185P 450 514 400 1600 400 315 30 15
6600-3200P
6600-3220P
6600-3250P
6600-3280P 450 514 400 1800 400 315 30 15
6600-3315P
6600-3355P
6600-3400P

Related Names
Variable Speed Drives | High-Performance Inverter | HVAC Inverter